Clear 21:
active filter error (only for
WO*A080LFCA and WO*A100LFTA)
PFC error (only for WO*A060LFCA)
Hydraulic Unit LED:
Green 6 flashes / Red 4 flashes
Outdoor Unit LED:
flash
Probable causes:
•
Connection failure
•
Active filter module failure (only for WO*A080LFCA and WO*A100LFTA)
•
Main PCB failure
Check:
Clear 21:
1 Check connections in control unit:
- Check if the terminal connection is loose
- Check if connector is removed
- Check if connector is erroneous connection
- Check if cable is open
Upon correcting the removed connector or mis-wiring, reset
the power
2 Replace Active Filter Module and Main PCB : (only 080 and 100)
If Check Point 1 does not improve the symptom, replace
Main PCB and Active Filter Module and execute the
checkoperation again
OK
Maintenance document "1792 - EN"
Split system single phase type
- 22 -
(only for
WOYA080LFCA and WOYA100LFTA)