Clear 26:
Low pressure abnormal
Hydraulic Unit LED:
Green 10 flashes / Red 5 flashes
Outdoor Unit LED:
flash
Probable causes:
•
Connector connection failure
•
Pressure Sensor failure
•
Main PCB failure
•
Gas leak, less
Check:
Clear 26:
OK
3 Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it
If recharging refrigerant, make sure to perform vacuuming and
recharge the specified amount
OK
1 Check connection of the Pressure Sensor:
- Check if the terminal connection is loose
- Check if connector is removed
- Check if connector is erroneous connection
- Check if cable is open
Upon correcting the removed connector or mis-wiring, reset the power
OK
4 Replace Pressure Sensor
If Check Point 1 ~ 3 do not improve the symptom, replace Pressure
Sensor
2 Check output voltage of Main PCB :
Check voltage of Main PCB (Measure at Main PCB side connector)
1 pin(Red) - 3 pin(Black) DC5V +/- 5%
WO*A060LFCA
WO*A080LFCA and WO*A100LFTA
If the voltage is not correct, replace Main PCB
PRESSURE
SENSOR
PRESSURE
SENSOR
Maintenance document "1792 - EN"