Operating Mode Changeover
Line N
°
Programming line
HC1
HC2
900
1200
Optg mode changeover
(None / Frost protection mode / Reduced / Comfort
/ Automatic)
In case of an external changeover via input H2 (on the
extension module only) the operating mode to which the
changeover will be performed must be previously defined.
Heating Circuit Frost Protection
The heating circuit frost protection is continuously
activated (protection mode ) and is not adjustable
Heating circuit frost protection in heating mode
If the flow temperature is below 5°C, the controller
initiates the production of heat and starts the heating
pumps, regardless of the current heating mode
If the flow temperature rises again above 7°C, the
controller waits another 5 minutes, and then stops the
production of heat and the heating pumps
Heating circuit frost protection in cooling mode
See Cooling mode
Maintenance document "1792 - EN"
- 69 -