Time program 4/DHW
Time program 4/DHW of the local controller is taken into
account for the heater
Information:
Switch-on will actually be in effect only if the heater is
able to operate according to the "heater operating mode"
setting
4 4 5
Configuration Functions
When an installation is started up, the hydraulic diagram
presetting for that installation must be entered
Presettings
Line N°
Programming line
5700
Pre-setting
Only Pre-setting 1 to 4 are used among 9 availables
Heating circuits/Cooling Circuit
Line N°
Programming line
5710
Heating circuit 1
5711
Cooling circuit 1 (Off / 4-pipe system / 2-pipe
system)
5715
Heating circuit 2
Heating circuit 1
Using this setting, heating circuit 1 can be switched on
and off
Cooling circuit 1
Off:
The cooling circuit is deactivated
4-pipe system:
Not compatible with the Waterstage heat pump This
setting relates to passive cooling
2-pipe system:
Activates the heat pump cooling mode However, the
cooling kit must have been previously connected
Warning:
If the cooling kit has not been connected and the cooling
mode is activated the heat pump will behave abnormally
and might cause some unwanted discomfort
Information:
Switching on the cooling mode causes the menu '"Cooling
circuit 1" to appear
Heating circuit 2
Using this setting, heating circuit 2 can be switched on
and off
DHW
Line N° PROGRAMMING LINE
5731 DHW ctrl elem Q3
• No charging request
No DHW charging via Q3
• Charging pump
DHW charging is effected with a pump connected to
terminal Q3
•
Diverting valve
DHW charging is effected with a diverting valve connected
to terminal Q3
Electric backup
Line N°
Programming line
5806
Type el imm heater flow
Within the type of electric backup, 4 settings are possible :
•
3-stage
Not used
•
2-stage excuding
Not used
•
2-stage complementary
The backup 1 starts alone, then the backup 2 starts alone,
then the two backups start simultaneously Exemple for
a 3kw backup and a 6kw backup, 1st stage : 3kw, 2nd
stage : 6kw, 3rd stage : 3+6=9kw
•
Modulating Ux
The backup 1 is regulated as required
Basic unit EX/E
Line N°
Programming line
5981
Cont type input EX1, EX2, EX3
5983
5985
The type of contact can be selected:
NC
The input’s function is active when voltage is not present
NO
The input’s function is active when voltage is present
The descriptions relating to the functions of the EX
contact apply when an NO contact is selected
Maintenance document "1792 - EN"
- 79 -