2 Fault
2 1 Fault List
2 1 1
Hydraulic Unit Fault
Faults which occur on the Hydraulic Unit are shown by
the symbol Press the info key for details on the cause
of the fault The following information is displayed :
• Description of the error
• Location of the error (sensor or contact)
• Reset Depending on its type, the fault can be manually
or automatically deleted:
• Manual delete: the text displayed when pressing the info
key shows "reset ?". Press OK once, the yes flashes;
press again to confirm deletion of the fault.
• Faults whose deletion is automatic are automatically
reset
• Heat pump op: shows whether or not the heat pump
operates despite the fault
No : Designation of error
Location (connection)
Reset
HP op
Manual
Auto
10: Outdoor sensor
X86
No
No
Yes
33: Flow sensor HP
X70
No
No
Yes
44: Return sensor HP
X70
No
No
Yes
50: DHW sensor 1
X84
No
No
Yes
60: Room sensor 1
No
No
Yes
65: Room sensor 2
No
No
Yes
105: Maintenance message
No
No
Yes
121: Flow temp HC1 (too low)
No
No
Yes
122: Flow temp HC2 (too low)
No
No
Yes
127: Legionella temp
No
No
Yes
369: External fault (safety component)
No
No
370: Thermodynamic source*
No
No
No
No connection
the polarity of the room
sensor is not respected
-
No
*
A fault in the outdoor unit is indicated by LED located on the Hydraulic Unit interface board.
Maintenance document "1792 - EN"
- 5 -
Split system single phase type