Warning :
This setting value is too small, the efficiency is decreased
due to the compressor frequency changes frequently
Release integr electric flow
After the release of the 1st stage (heater 1:on, heater
2:off), the controller compares the temperature measured
with the point of engagement and forms an integral and
includes a possible deficit of heat. Once the value of
the integral reaches the maximum value (2882), the
2nd stage is engaged (heater 1:off, heater 2:control)
The controller continuously compares the temperature
measured at the point of engagement and new features
to the deficit of heat in the full release.
When the full release reaches the value set (2882), the
3rd stage of the heater is triggered (heater 1:fixed on,
heater 2:control)
Flow elec. release at OT
The heater will be activated only if the attenuated outdoor
temperature is below the temperature set here
Warning:
If this setting is too low, there may be a feeling of
discomfort due to the fact that the heat pump is unable
to meet the heating requirements alone at low outdoor
temperatures, and heaters are not switched on
Compensation heat deficit
This function compensates for excess heat and heat
deficits. These can occur in the following situations: •
Minimum compressor on and off times
• In the case of low temperature requests, the flow
temperature can lie below the required setpoint, but the
return temperature may not drop below the switchon oint
for a longer period of time In this situation, the heat
pump must be switched on to prevent heat deficits The
controller compares continuously the flow temperature
setpoint with the actual value and integrates the surplus
heat and heat deficits. Differences are compensated for
by extending the compressor on and off times If the
compressor is not switched on or off due to surplus heat/
heat deficits, the controller displays an appropriate status
message This function is not active during the time the
DHW storage tank is charged The function is not active
either in the case of plants with buffer/(combi) storage
tanks. "Compensation heat deficit" only acts in heating
mode The parameter is inactive in cooling mode The
maximum switch-off temperature is given priority over the
"Compensation" function In the case of sudden setpoint
changes, both integrals are cleared
•
Behavior in connection with the "Floor curing"
function
When activating the "Floor curing" function, the integral
is set to a level representing 1.5 times the predefined
value (factory setting) If the current temperature lies at
least 2 K below the required setpoint, the heat pump is
immediately switched on
If compensation of surplus heat/heat deficits shall act
"Only with floor curing fct", the respective setting must be
selected This means that the parameter is deactivated
in normal heating mode
•
Calculation of integral
If a flow temperature sensor (BX1) is connected and the
heating curve is set to the flow temperature setpoint,
the controller uses the flow temperature and the flow
temperature setpoint for computing the integrals In the
following situations, the integral is set to "0":
- No valid temperature request delivered
- Setpoint change >2 K
- Frost protection for the heat pump is active
- The heat pump has gone to lockout or cannot deliver
any heat for a longer period of time
- The heat pump is in active cooling mode
- A buffer storage tank is being charged
- The function is deactivated
With active DHW charging, the integral value is frozen.
With electrical utility lock
This setting relates to input Ex1 (load-shedding or peak
day clearing) and allows the electric heaters to be locked
as follows:
• Locked:
The heat pump and all electric heaters are locked, both
heat pump stages and the DHW tank electric auxiliary
Only the boiler backup, if installed, continues to operate
• Released
The heat pump operates and all electric heaters are
locked, both heat pump stages and the DHW tank electric
auxiliary
The boiler backup, if installed, continues to operate
Maintenance document "1792 - EN"
Split system single phase type
- 76 -