Chapter 5
Replacing Cold-Swappable FRUs
5-3
Note –
You can also use the Power On/Off button on the front of the server to
initiate a graceful system shutdown. This button is recessed to
prevent accidental server power-off. Use the tip of a pen to operate this button.
Refer to the
Advanced Lights Out Management (ALOM) CMT Guide
for more
information about the ALOM CMT
poweroff
command.
5.1.3
Extending the Server to the Maintenance Position
If the server is installed in a rack with the extendable slide rails that were supplied
with the server, use this procedure to extend the server to the maintenance position.
Note –
Remove the server from the rack for all cold-swappable FRU replacement
procedures except the DIMMs, PCI cards, and the system controller.
1. (Optional) Issue the following command from the ALOM CMT
sc>
prompt to
locate the system that requires maintenance.
Once you have located the server, press the Locator LED button to turn it off.
2. Check to see that no cables will be damaged or interfere when the server is
extended.
Although the cable management arm (CMA) that is supplied with the server is
hinged to accommodate extending the server, ensure that all cables and cords are
capable of extending.
3. From the front of the server, release the slide rail latches on each side.
Pinch the green latches as shown in
sc>
setlocator on
Locator LED is on.
Summary of Contents for SPARC Enterprise T2000
Page 1: ......
Page 2: ......
Page 6: ......
Page 16: ...xiv SPARC Enterprise T2000 Server Service Manual April 2007 ...
Page 18: ...xvi SPARC Enterprise T2000 Server Service Manual April 2007 ...
Page 27: ...Preface xxv Reader s Comment Form ...
Page 43: ...Chapter 3 Server Diagnostics 3 3 FIGURE 3 1 Diagnostic Flow Chart flowchart ...
Page 106: ...4 12 SPARC Enterprise T2000 Server Service Manual April 2007 ...
Page 152: ...5 46 SPARC Enterprise T2000 Server Service Manual April 2007 ...
Page 173: ......
Page 174: ......