140
Upgrade and Maintenance Manual
RX300
S8
Hard disk drives / solid state drives
Ê
Wait about 30 seconds to allow the hard disk drive to spin down.
I
This is not necessary when removing a solid state drive.
Figure 48: Removing a 2.5-inch HDD / SSD module
Ê
Pull the HDD / SSD module completely out of its bay.
7.3.3.3
Installing a 2.5-inch dummy module
V
CAUTION!
If the removed HDD / SSD module is not replaced immediately, always
replace a dummy module into the unused HDD / SSD bay to comply with
applicable EMC regulations and satisfy cooling requirements.