CX2550 M1
Upgrade and Maintenance Manual
189
Liquid cooling
10.1.2 Replacing the liquid cooling kit
10.1.2.1 Preliminary steps
Ê
"Disabling SVOM boot watchdog functionality" on page 54
Ê
"Shutting down the server node" on page 39
Ê
Disconnect the tubes from the tube system of the rack as described in the
"RackCDU
TM
Service Manual".
Ê
"Removing the server node from the server enclosure" on page 40
10.1.2.2 Removing the liquid cooling kit
Figure 80: Removing the riser module
Ê
Remove both riser modules (1, 2) as described in chapter
"Removing the
riser module" on page 41
.
I
The connection of the flexible tubes to the liquid cooling system of the
rack you may find in the corresponding manual of the rack.
Field Replaceable Unit
(FRU)
Hardware: 15 minutes
Software: 5 minutes
Tools:
Phillips PH2 / (+) No. 2 screw driver