CX2550 M1
Upgrade and Maintenance Manual
65
Basic software procedures
5.2.1.2
Updating or recovering the iRMC
iRMC flash procedure
I
For the Japanese market, follow the instructions provided separately.
Ê
Prepare a USB stick including the bootable iRMC firmware update image.
Ê
Connect the USB stick to the USB port.
I
Ensure that only the USB device with the iRMC firmware is connected
to the USB port. Remove all other USB devices temporarily.
Ê
Restart the server.
Ê
The system will detect the USB stick.
I
If the BIOS cannot identify the USB stick, the pop-up message
Failed to boot for Emergency flash. Please Reset now
.
will show up in the center of the screen.
Ê
Choose one of the following options from the update tool menu to start the
iRMC update process:
Normal
Choose this option to update an existing system board.
Initial
Choose this option if the system board has been replaced prior to the
iRMC update procedure. This option will perform all relevant flash
procedures in a row, including the iRMC firmware and bootloader.
V
CAUTION!
Do not interrupt the iRMC upgrade process after it has started. If the
process is interrupted, the iRMC BIOS may be permanently
corrupted.
I
If the iRMC does not work after flashing, disconnect the system from
the mains and reconnect it again.
Ê
After completion of the flash process, remove the USB stick and restart the
server.
iRMC recovery procedure
I
For the Japanese market, follow the instructions provided separately.
Ê
Prepare a USB stick including the bootable iRMC firmware update image.
Summary of Contents for PRIMERGY CX2550 M1
Page 14: ...Upgrade and Maintenance Manual CX2550 M1 Contents ...
Page 52: ...52 Upgrade and Maintenance Manual CX2550 M1 Basic hardware procedures ...
Page 90: ...90 Upgrade and Maintenance Manual CX2550 M1 Basic software procedures ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 M1 Liquid cooling ...
Page 210: ...210 Upgrade and Maintenance Manual CX2550 M1 Cabling ...
Page 222: ...222 Upgrade and Maintenance Manual CX2550 M1 Appendix ...