2-16. E: 53. Drain pump error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 53
Detective actuator
Indoor unit main PCB
When Float switch is ON for more than 3 minutes.
Float switch
Forecast of cause
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
Check point 1. Check float switch
•
Check operation of float switch. (any blocking by dust, etc.)
•
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
↓
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
↓
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
↓
Check point 4. Check voltage of power supply and drain pump
Check drain pump
-> If drain pump is not run on the working condition, check the voltage of the CN71
on the main PCB.
Measurement result
•
12V: Replace the drain pump
•
Other than 12V: Replace the main PCB
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-24.
↓
End
2-16. E: 53. Drain pump error (Indoor unit)
- (03-21) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...