Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
Setting procedure by using remote controller
Remote controller is not attached for this product. For details of the installing remote controller, refer
to following information.
• Overview information: Operating manual of the remote controller
• Setting procedure: Installation manual of the remote controller
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
11
Filter sign
2)
20
Ceiling height
3)
22
Outlet directions
4)
23
Vertical airflow direction range control
5)
30/31
Room temperature control for indoor unit sensor
6)
35/36
Room temperature control for wired remote controller sensor
7)
40
Auto restart
8)
42
Room temperature sensor switching
9)
44
Remote controller custom code
10)
46
External input control
11)
48
Room temperature sensor switching (Aux.)
12)
49
Indoor unit fan control for energy saving for cooling
13)
60
Switching functions for external output terminal
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (2,500 hours)
01
Long interval (4,400 hours)
02
Short interval (1,250 hours)
03
No indication
♦
1-1. Function settings on indoor unit
- (05-3) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...