5) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is “03”
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
1-1. Function settings on indoor unit
- (05-5) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...