Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
AUXG36KRLB
A zone
98
64
49
32
B zone
98
64
49
32
C zone
77
49
40
32
D zone
54
40
34
26
E zone
54
40
34
26
F zone
54
40
34
26
AUXG45KRLB
A zone
114
79
61
40
B zone
114
79
61
40
C zone
96
61
49
40
D zone
67
49
42
32
E zone
67
49
42
32
F zone
67
49
42
32
AUXG54KRLB
A zone
95
66
51
33
B zone
95
66
51
33
C zone
80
51
41
33
D zone
56
41
35
27
E zone
56
41
35
27
F zone
56
41
35
27
1-1. Cooling operation
- (04-2) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...