2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number
Setting value
Setting description
Factory setting
20
00
Standard
♦
01
High ceiling
02
Low ceiling
For the specific height for each setting value, refer to “Installation space” in Chapter "Dimensions" on
page 1.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number
Setting value
Setting description
Factory setting
22
00
4-way
♦
01
3-way
4) Vertical airflow direction range control
To prevent draft, change the setting to "Upward" (01).
Note that the airflow in certain usage conditions may leave the ceiling dirty. In such cases, the use of
the optional Panel spacer is recommended.
Function number
Setting value
Setting description
Factory setting
23
00
Standard
♦
01
Upward
Ceiling
Swing scope (standard)
Swing scope (upward)
1-1. Function settings on indoor unit
- (05-4) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...