Overflow control
•
Triggering condition
The float switch is turned on.
•
Operation details
– The drain pump is turned on.
– When the operation mode is cooling or dry, operate the followings.
• The compressor is stopped.
• Then indoor fan control is turned off.
•
Release condition
– The float switch is turned off.
• In the case that on the cooling or dry mode the thermostat is on, refer to "
" for the operation after release.
When the compressor is not in operation
release.
– 3 minutes passed
•
Operation after release
The compressor stopps permanently.
The compressor is stopped by Anti-freezing control
•
Triggering condition
During the compressor in operation, the compressor is stopped by Anti-freezing control.
•
Operation details
The drain pump is kept on in 60 minutes after Anti-freezing control released.
•
Release condition
60 minutes passed
•
Operation after release
According to the settings, operate the followings.
On
Off
On
Off
On
Off
a. Operation at
anti-freezing
b. Operation when
cooling mode is
stopped
Operation at
a. and b.
60
3
7
3
3
47
3
117
(min)
3
2
3
60
117
Anti-freezing start
Stopped
Release
freezing
7-8. Drain pump control
- (04-30) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...