1-2. Outdoor unit
Type
Inverter heat pump
Model name
AOYG36KQTA
Power supply
3N 400 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
342—457 V
Starting current
A
5.9
Fan
Airflow rate
Cooling
m
3
/h
3,750
Heating
3,750
Type × Q'ty
Propeller × 1
Motor output
W
100
Sound pressure level *1
Cooling
dB (A)
55
Heating
55
Sound power level
Cooling
dB (A)
70
Heating
70
Heat exchanger type
Dimensions
(H × W × D)
mm
Main 1: 756 × 905 × 18.19
Main 2: 756 × 905 × 18.19
Fin pitch
Main 1: 1.45
Main 2: 1.45
Rows × Stages
Main 1: 1 × 36
Main 2: 1 × 36
Pipe type
Copper
Fin
Type (Material)
Aluminum
Surface treatment
Blue fin
Compressor
Type × Q'ty
DC Twin rotary × 1
Motor output
W
1,500
Refrigerant
Type (Global warming potential)
R32 (675)
Factory charge
g
1,900
Refrigerant oil
Type
FW68D
Amount
cm
3
600
Enclosure
Material
Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
788 × 940 × 320
Gross
966 × 1,027 × 445
Weight
Net
kg
53
Gross
62
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (3/8)
Gas
Ø 15.88 (5/8)
Method
Flare
Pre-charge length
m
30
Max. length
30
Max. height difference
30
Operation range
Cooling
°C
-10 to 46
Heating
-15 to 24
Drain hose
Material
LDPE
Size
mm
Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• This data is based on EN 14511 standard.
1-2. Outdoor unit
- (01-3) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...