DIP switch setting
•
SW100: Remote controller address setting
When operating a number of indoor units by using a wired remote controller, DIP switch set-
ting for assigning unit number to each indoor unit is required.
The slide switches are normally set to make the unit number 00.
Remote
controller
address
Switch number
Factory setting
1
2
3
4
00
OFF
OFF
OFF
OFF
♦
01
ON
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
03
ON
ON
OFF
OFF
04
OFF
OFF
ON
OFF
05
ON
OFF
ON
OFF
06
OFF
ON
ON
OFF
07
ON
ON
ON
OFF
08
OFF
OFF
OFF
ON
09
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
00
01
02
Remote controller address
Indoor unit
Remote controller
•
SW101-Switch 1: Setting change prohibited
•
SW101-Switch 2: Setting change prohibited
•
SW101-Switch 3: Fan delay setting
When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor
unit fan operation will continue for 1 minute.
Switch 3
Fan delay
Factory setting
ON
Enabled
OFF
Disabled
♦
1-1. Function settings on indoor unit
- (05-2) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...