Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG54KQTA
A zone
50 rps
B zone
47 rps
C zone
40 rps
D zone
30 rps
E zone
22 rps
F zone
20 rps
G zone
16 rps
H zone
16 rps
I zone
17 rps
J zone
23 rps
K zone
28 rps
1-5. Compressor frequency limitation by outdoor temperature