1-6. OUTDOOR FAN CONTROL
1. Fan Speed
Following table shows the fan speed of the outdoor unit.
( Table 7 : Fan speed of the outdoor unit )
Upper fan
Lower fan
The outdoor fan speed is decided depending on the compressor and the outdoor temperature.
The compressor and the fan start-up at the same time,
and the fan stops after the compressor stops and 60 seconds has passed.
Cooling
850/ 780/ 520/ 480/ 400/ 350/ 280 rpm
800/ 750/ 520/ 350/ 280/ 0 rpm
AOU30RLXEH
Upper fan
Lower fan
Heating
870/ 780/ 520/ 350/ 200/ 170/ 150 rpm
840/ 750/ 520/ 350/ 200/ 170/ 150 rpm
AOU30RLXEH
.
.
01-07