Compressor
ON
OFF
Indoor fan
Setting air flow
OFF
10
30
60
180
60
180
60 10
30
(sec)
S-Lo
480rpm
( Fig.9 : Indoor fan control )
9. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig. 9.
( Factory setting)
Setting Description
Function Number
Setting Value
Disable
Enable
Remote controller
49
02
00
01
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02 : Enable or disable this function by remote controller setting.
Set to “00”or “01”when connecting a remote controller that cannot set
the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting,
refer to the operating manual of each remote controller.
Switch the airflow [AUTO] at cooling mode, addition, in the case of Energy saving setting "ON"
and the indoor fan motor will run as shown in Fig. 8.
8. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig. 8 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(SEC)
( Table 6 : Indoor fan speed )
X zone
J zone
Y zone
ASU30RLE
780rpm
680rpm
540rpm
780rpm
Dry
Cooling
01-06
Summary of Contents for AOU30RLXEH
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Page 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Page 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Page 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...