OK
OK
OK
OK
1. External cause 2. Connector connection failure 3. Main PCB failure 4. Active filter module failure
5. Transistor PCB failure
Test 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
Test 4 : Check Transistor PCB
Test 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Test 5 : Replace Main PCB
If Test 1 - 4 do not improve the symptom, change Main PCB.
OK
OK
Test 3 : Check Active filter module
Check Active filter module.
>>If Active filter module is abnormal, replace it.
Check Transistor PCB
>>If Transistor PCB is abnormal, replace it.
Trouble shooting 16
OUTDOOR UNIT Error Method:
Active Filter Error
Outdoor unit main PCB
Active filter module
Transistor PCB
①
When inverter input DC voltage is higher than 430V or lower than 110V.
②
When a momentary power cut off occurred on low voltage.
Detective Actuators:
Detective details:
Indicate of Display:
Forecast of Cause:
Outdoor unit : No indication
02-19
Indoor Unit :
Operation lamp: 6 times Flash,
Timer lamp : 4 times Flash
ERROR CODE : [E : 64]
Summary of Contents for AOU30RLXEH
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Page 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Page 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Page 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...