Test 1 : Check rotation of Fan
Test 2 : Check ambient temp. around motor
OK
OK
OK
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Power Supply PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace It.
Check excessively high temperature around the motor.
(if there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Test 4 : Replace Power Supply PCB
If Test 1- 3 do not improve the symptom, replace Power Supply PCB.
Test 3 : Check Indoor unit fan motor
Check Indoor unit fan motor.
>>if Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Trouble shooting 13
INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Indoor unit power supply PCB
Indoor unit fan motor
When the fan motor speed is less than 1/3 of the target fan speed
for 56 seconds.
When detect the 0 rpm for 56 seconds after fan motor started.
Detective Actuators:
Detective details:
Indicate of Display:
Forecast of Cause:
(SERVICE PARTS INFORMATION 4)
02-16
n: n times blinking
: Light ON
: Light OFF
Outdoor unit :
POWER
MODE
ERROR
2
5
(L1)
(L2)
(L6)
(L5)
(L4)
(L3)
15
PUMP
DOWN
LOW
NOISE
PEAK
CUT
Indoor Unit :
Operation lamp: 5 times Flash,
Timer lamp : 1 times Flash
ERROR CODE : [E : 51]
Summary of Contents for AOU30RLXEH
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Page 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Page 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Page 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...