Heat Sink Thermistor Error
Inverter PCB
Heat sink temperature thermistor (Built-in IPM) open/short detected
1. Inverter PCB failure
02-26
Trouble shooting 23
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
If this error is displayed, replace Inverter PCB
Indicate or Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp : 7 times Flash
ERROR CODE : [E : 77]
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
7
L1 L2
3
L
4
L
5
L
6
L
7
Outdoor unit :