3-2. Outdoor unit—No power
Forecast of cause
Power supply failure
External cause
Electrical components defective
Check point 1. Check installation condition
•
Is the circuit breaker on or off?
•
Check loose or removed connection cable.
If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN &
TECHNICAL MANUAL”.
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 198 to 264 V appears at outdoor unit terminal L - N
and
.
+
-
•
Check fuse in main PCB.
If fuse is open, check if the wiring between terminal and main PCB is loose, and replace fuse.
Check point 4. Replace main PCB
If check point 1 to 3 do not improve the symptom, change main PCB.
End
3-2. Outdoor unit—No power
- (03-37) -
3. Troubleshooting without error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ADUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AR030EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AR030EF_01 ...
Page 49: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AR030EF_01 ...
Page 52: ......
Page 110: ...5 2 Outdoor unit 03 58 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 111: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AR030EF_01 ...
Page 145: ...5 FILED WORKING 2021 04 26 SR_CH05_AR030EF_01 ...