2-12. E: 41. Room temperature sensor error (Indoor unit)
Indicator
→ired remote
controller
Error code
E: 41
Detective actuator Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-24.
If the voltage does not appear, replace main PCB.
End
2-12. E: 41. Room temperature sensor error (Indoor unit)
- (03-16) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ADUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AR030EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AR030EF_01 ...
Page 49: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AR030EF_01 ...
Page 52: ......
Page 110: ...5 2 Outdoor unit 03 58 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 111: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AR030EF_01 ...
Page 145: ...5 FILED WORKING 2021 04 26 SR_CH05_AR030EF_01 ...