Temperature set back timer
• The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start
or stop air conditioner operation.
• The SET BACK timer can be set to operate up to two times per day but only one temperature
setting can be used.
• During COOLING/DRY mode, the air conditioner will operate at a minimum of 64°F (18°C)
even if the SET BACK temperature is set to 63°F (17°C) or lower.
Case of SET BACK timer on the Cooling operation. (Setting temperature :72°F [22°C], SET
BACK temperature :78°F [26°C])
SET BACK setting
Operation
temperature
Operation
temperature
*1
ON
OFF
OFF
ON
*1: During the SET BACK function,
the setting temperature is changed.
Chenge the setting temperature:
72°F (22°C) 75°F (24°C)
72°F (22°C)
78°F (26°C)
75°F (24°C)
72°F (22°C)
78°F (26°C)
4-2. →ired remote control
- (04-20) -
4. Timer operation control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for ADUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AR030EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AR030EF_01 ...
Page 49: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AR030EF_01 ...
Page 52: ......
Page 110: ...5 2 Outdoor unit 03 58 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 111: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AR030EF_01 ...
Page 145: ...5 FILED WORKING 2021 04 26 SR_CH05_AR030EF_01 ...