19) Fan delay time
Sets the fan delay time when the heater is turned off.
Function number
Setting value
Setting description
Factory setting
74
00
1 minute
♦
01
50 seconds
02
40 seconds
03
30 seconds
20) External heater use in defrosting
Enables or disables external heater use in defrosting.
NOTE:
Inappropriate heater selection may cause cold air in defrosting.
Function number
Setting value
Setting description
Factory setting
75
00
Disable
♦
01
Enable
1-2. Function settings by using remote controller