2-18. E: 64. PFC circuit error (Outdoor unit)
Indicator
→ired remote
controller
Error code
E: 64
Detective actuator Outdoor unit
Main PCB
•
→hen inverter input DC voltage is higher than 415
V for over 3 seconds, the compressor stops.
•
If the same operation is repeated 5 times, the
compressor stops permanently.
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 2. Check connection of Connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace main PCB
If check point 1 to 2 do not improve the symptom, change main PCB.
End
2-18. E: 64. PFC circuit error (Outdoor unit)
- (03-22) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ADUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AR030EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AR030EF_01 ...
Page 49: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AR030EF_01 ...
Page 52: ......
Page 110: ...5 2 Outdoor unit 03 58 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 111: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AR030EF_01 ...
Page 145: ...5 FILED WORKING 2021 04 26 SR_CH05_AR030EF_01 ...