1-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
¢
Setting procedure by using remote controller
Remote controller is not attached for this product. For details of the installing remote controller, refer
to following information.
• Overview information: Operating manual of the remote controller
• Setting procedure: Installation manual of the remote controller
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
11
Filter sign
2)
26
Static pressure
3)
30/31
Room temperature control for indoor unit sensor
4)
35/36
Room temperature control for wired remote controller sensor
5)
40
Auto restart
6)
42
Room temperature sensor switching
7)
44
Remote controller custom code
8)
46
External input control
9)
48
Room temperature sensor switching (Aux.)
10)
49
Indoor unit fan control for energy saving for cooling
11)
60
Switching functions for external output terminal
12)
61
Control switching of external heaters
13)
62
Operating temperature switching of external heaters
14)
66
Outdoor temperature zone boundary temperature A
15)
67
Outdoor temperature zone boundary temperature B
16)
71
Standby time for auxiliary equipment operation
17)
72
Heat pump backup setting
18)
73
Emergency heat
19)
74
Fan delay time
20)
75
External heater use in defrosting
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
1-2. Function settings by using remote controller
- (05-3) -
1. Function settings
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Summary of Contents for ADUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AR030EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AR030EF_01 ...
Page 49: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AR030EF_01 ...
Page 52: ......
Page 110: ...5 2 Outdoor unit 03 58 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 111: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AR030EF_01 ...
Page 145: ...5 FILED WORKING 2021 04 26 SR_CH05_AR030EF_01 ...