2-32. E: A3. Compressor temperature error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: A3
Detective actuator
Outdoor unit main PCB
Protection stop by compressor temperature ≥ 108 °C
during compressor operation generated 2 times within
24 hours.
Compressor temperature thermistor
Forecast of cause
3-way valve not opened
EEV defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Compressor temperature thermistor failure
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
↓
Check point 3. Check the outdoor unit fan and heat exchanger
•
Check for foreign object at heat exchanger
•
Check if fan can be rotated by hand.
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the compressor thermistor
The compressor temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
↓
2-32. E: A3. Compressor temperature error (Outdoor unit)
- (03-39) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...