2-33. E: AC. Heat sink temperature error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: AC
Detective actuator
Outdoor unit inverter PCB
Protection stop by heat sink temperature ≥ 80 °C during
heat sink operation generated 2 times within 24 hours.
Heat sink temperature thermistor
Forecast of cause
Foreign matter on heat sink, heat sink dirty
Foreign matter on heat exchanger, excessive ambient
temperature rise
Heat sink temp. thermistor defective
Check point 1. Check the heat sink state
Heat sink foreign matter, soiling check
↓
Check point 2. Check the foreign matter and ambient temperature of heat exchanger
•
Heat exchange foreign matter check
•
Ambient temperature not raised by effect of other heat sources?
•
Discharged air not sucked in?
↓
Check point 3. Check the heat sink temperature thermistor
The heat sink temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
↓
Check point 4. Replace inverter PCB
Replace inverter PCB
↓
End
2-33. E: AC. Heat sink temperature error (Outdoor unit)
- (03-41) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...