2-29. E: 97. Outdoor unit fan motor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 97
Detective actuator
Outdoor unit
Main PCB
1. When outdoor fan rotation speed is less than 100
rpm in 20 seconds after fan motor starts, fan motor
stops.
2. After fan motor restarts, if the same operation within
60 seconds is repeated 3 times in a row,
compressor and fan motor stops.
3. If 1. and 2. repeats 5 times in a row, compressor
and fan motor stops permanently.
Fan motor
Forecast of cause
Fan rotation failure
Motor protection by surrounding temperature rise
Main PCB failure
Outdoor unit fan motor
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check outdoor unit fan motor
Check outdoor unit fan motor. (Refer to outdoor unit fan motor in
page 03-49.)
→ If outdoor unit fan motor is abnormal, replace outdoor unit fan motor and main PCB.
↓
Check point 4. Check output voltage of main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at main PCB side con-
nector)
NOTE:
For details of wiring diagram, refer to
TECHNICAL DATA AND PARTS LIST on page 02-13.
Read wire
DC voltage
Red—Black
306 V (DC 340 V -10%) to 374 V (DC 340 V +10%)
White—Black
15 ± 1.5 V
-> If the voltage is not correct, replace Main PCB.
↓
End
2-29. E: 97. Outdoor unit fan motor error (Outdoor unit)
- (03-34) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...