¢
Forced thermostat off function
Function
setting /
Rotary SW of External
input and output PCB
External input
Input signal
Command
60-00 / 2
External input and output
PCB
Input 1
Off → On
Thermostat off
60-09 / B
60-10 / C
On → Off
Normal
operation
60-11 / D
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
¢
Control output function
Function
setting /
Rotary SW of External
input and output PCB
External output
Output signal
Command
60-00 / 1, 2
Output of indoor unit
CN47
Low → High
Operation
High → Low
Stop
60-00 / 1
External input and output
PCB
Output 1
Off → On
Operation
60-09 / B
60-10 / C
On → Off
Stop
60-11 / D
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit
3-4. Details of function
- (05-18) -
3. External input and output for indoor unit
FIELD
WORKING
FIELD
WORKING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...