2-4. E: 15. Automatic air flow adjustment error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 15
Detective actuator
Indoor unit
Main PCB
•
On automatic airflow adjustment operation, when
the fan speed other than 0rpm is detected at the
0rpm operation.
•
On automatic airflow adjustment operation, when
the fan speed is not reach the target speed, after 2
minutes from the fan started.
•
On automatic airflow adjustment operation
operation, when the 72:750W,90:1000W of input
power is detected.
Forecast of cause
Fan rotation failure
Fan motor winding open
Indoor unit main PCB
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
"Error code table (Outdoor unit)"
page 03-2.)
→ If indoor unit fan motor is abnormal, replace it.
↓
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.
↓
End
2-4. E: 15. Automatic air flow adjustment error (Indoor unit)
- (03-9) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...