1. Specifications
1-1. Indoor unit
Type
Ceiling
Inverter heat pump
Model name
ABHG54KRTA
Power supply
3N 400 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
342—457 V
Capacity
Cooling
Rated
kW
13.4
Btu/h
45,700
Min.—Max.
kW
4.5—14.5
Btu/h
15,350—49,400
Heating
Rated
kW
15.5
Btu/h
52,900
Min.—Max.
kW
4.7—16.5
Btu/h
16,040—56,310
Input power
Cooling
Rated
kW
4.45
Max.
5.23
Heating
Rated
4.43
Max.
4.83
Current
Cooling
Rated
A
8.0
Heating
8.0
EER
Cooling
kW/kW
3.01
COP
Heating
3.50
Power factor
Cooling
%
80.5
Heating
80.4
Moisture removal
L/h (pints/h)
5.0 (8.8)
Maximum operating current *
1
Cooling
A
14.0
Heating
14.0
Fan
Airflow rate
Cooling
HIGH
m
3
/h
2,100
MED
1,700
LOW
1,500
QUIET
1,220
Heating
HIGH
2,100
MED
1,700
LOW
1,500
QUIET
1,220
Type × Q'ty
Sirocco × 4
Motor output
W
130
Sound pressure level *
2
Cooling
HIGH
dB (A)
48
MED
44
LOW
41
QUIET
38
Heating
HIGH
48
MED
44
LOW
41
QUIET
38
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,335 × 39.9
Fin pitch
mm
1.30
Rows × Stages
3 × 14
Pipe type
Copper
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
235 × 1,700 × 705
Gross
330 × 1,785 × 825
Weight
Net
kg
38
Gross
48
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas
Ø15.88 (Ø5/8)
Method
Flare
Drain hose
Material
PVC
Tip diameter
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-1) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...