7-8. Electronic expansion valve control
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the table below.
Operation mode
Pulse range
Cooling/dry mode
Between 47 and 480 pulses
Heating mode
Between 39 and 480 pulses
NOTE:
At the time of supplying the power to the outdoor unit, the initialization of the electronic ex-
pansion valve is operated (528 pulses are input to the closing direction).
7-8. Electronic expansion valve control
- (04-22) -