2-25. E: 86. High pressure switch error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 86
Detective actuator
Outdoor unit main PCB
When pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
•
Check connector and wiring connection state.
•
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Check the high pressure switch characteristics
•
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
↓
Check point 3. Replace main PCB
Change main PCB and check operation again.
↓
End
• Type of contact
C
H
Pressure
• Characteristics of pressure switch
Pressure switch 1
Contact: Short → Open
4.2±0.1 MPa
Contact: Open → Short
3.2±0.15 MPa
54 model: P770
2-25. E: 86. High pressure switch error (Outdoor unit)
- (03-30) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...