2-28. E: 95. Compressor motor control error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 95
Detective actuator
Outdoor unit
Main PCB
"Protection stop by "overcurrent generation at inverter
compressor starting" restart" generated consecutively 10
times x 3 sets (total 30 times)
Compressor
Forecast of cause
Defective connection of electric components
Main PCB failure
Compressor failure
Check point 1. Check Noise from Compressor
Turn on Power and check operation noise.
→ If an abnormal noise show, replace compres-
sor.
↓
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
↓
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
↓
End
2-28. E: 95. Compressor motor control error (Outdoor unit)
- (03-33) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...