2. CURRENT RELEASE CONTROL
05-17
[ Heating ]
AB*45LBAG
T0 >
12°C
T0 <
12°C
=
T0: Outdoor temperature
780 rpm
850 rpm
350 rpm
200 rpm
150 rpm
23.5A / 23.0A 20.0A / 19.5A
23.5A / 23.0A 23.5A / 23.0A 23.5A / 23.0A 23.5A / 23.0A
20.0A / 19.5A 15.0A / 14.5A 12.0A / 11.5A
Outdoor unit fan speed
[ Cooling ]
AB*45LBAG
T0 >
45°C
=
T0: Outdoor temperature
780 rpm
850 rpm
400 rpm
350 rpm
300 rpm
12.0A / 11.5A
20.0A / 19.5A 20.0A / 19.5A
23.5A / 23.0A
12.0A / 11.5A 12.0A / 11.5A
18.0A / 17.5A
20.0A / 19.5A
12.0A / 11.5A
18.0A / 17.5A
12.0A / 11.5A
15.0A / 14.5A
18.0A / 17.5A
Outdoor unit fan speed
[ Cooling ]
AB*30LBAG
AB*36LBAG
T0 >
45°C
T0 <
0°C
T0 <
13°C
45°C >
T0 >
38°C
=
=
45°C >
T0 >
38°C
=
38°C >
T0 >
31°C
=
31°C >
T0 >
25°C
=
25°C >
T0 >
19°C
=
19°C >
T0 >
13°C
=
13°C >
T0 >
0°C
=
19°C >
T0 >
13°C
=
38°C >
T0 >
19°C
=
T0: Outdoor temperature
780 rpm
850 rpm
400 rpm
250 rpm
170 rpm
10.0A / 9.5A
14.0A / 13.5A 14.0A / 13.5A
15.0A / 14.5A
18.0A / 17.5A
10.0A / 9.5A 10.0A / 9.5A
15.0A / 14.5A
7.0A / 6.5A
12.0A / 11.5A
5.5A / 5.0A
7.0A / 6.5A
9.5A / 9.0A
Outdoor unit fan speed
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 13 : Current Release Operation Value / Release Value)
[ Heating ]
AB*30LBAG
AB*36LBAG
T0 >
16°C
T0 <
5°C
16°C >
T0 >
5°C
=
=
T0: Outdoor temperature
780 rpm
900 rpm
400 rpm
250 rpm
170 rpm
15.0A / 14.5A 15.0A / 14.5A
18.0A / 17.5A 18.0A / 17.5A
18.0A / 17.5A
18.0A / 17.5A
13.0A / 12.5A 10.0A / 9.5A
8.0A / 7.5A
18.0A / 17.5A
Outdoor unit fan speed
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...