Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 :
Check Indoor Unit electric components
YES
YES
NO
Trouble shooting 8
INDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : Operation LED: Blink, Timer LED: Blink,
Vertical swing LED: OFF
Outdoor Unit : No indication
Indoor EEPROM abnormal
(Model No.)
Indoor Unit Controller PCB circuit
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure : Check if there is a defective contact
or leak current in the power supply
circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a non-
volatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When the model information being read from EEPROM has
an apparent error.
07-09
Indicate or Display:
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...