Trouble shooting 15
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Outdoor Unit : No indication
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Active Filter Module
OK
OK
OK
OK
OK
OK
Active Filter Module (AFM) error
Outdoor Unit Main PCB Circuit
Active Filter Module
1. External cause 2. Connector connection failure 3. Active Filter Module failure
4
. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Active Filter Module.
(PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
07-16
When inverter input DC voltage is higher than 467V or
lower than 237V.
When a momentary power cut off occurred on low voltage.
Indoor Unit : Operation LED: Blink, Timer LED: 12 times blink,
Vertical swing LED: OFF
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...