7. TROUBLESHOOTING
07-01
7-1 ERROR DISPLAY
7-1-1 INDOOR UNIT DISPLAY
Communication error
(Serial reverse transfer error)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature
sensor open
Indoor heat exchanger temperature
sensor short-circuited
Outdoor heat exchanger temperature
sensor error
Outdoor temperature sensor error
Outdoor discharge pipe temperature
sensor error
Indoor EEPROM abnormal (Model No.)
Indoor fan motor abnormal
Outdoor unit fan motor error
Outdoor communication signal error
(Forward transfer signal error)
Pressure switch error
Active filter module (AFM) error
CT error
IPM error
Compressor rotor location cannot detect
(permanent stop)
Compressor temperature sensor
error
8
3
4
2
5
6
7
9
10
11
12
13
14
15
16
17
0.5sec
0.5sec
5sec
ON
OFF
0.1sec
0.1sec
ON
OFF
1. ERROR DISPLAY
2. ERROR DISPLAY METHOD
1. ERROR DISPLAY
Error Contents
2 times blink
2 times blink
3 times blink
3 times blink
5 times blink
6 times blink
5 times blink
3 times blink
4 times blink
5 times blink
8 times blink
9 times blink
10 times blink
11 times blink
12 times blink
13 times blink
14 times blink
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Trouble
shooting
Vertical
Swing LED
Timer LED
Operation
LED
Please refer the blinking pattern as follows.
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
Continuous
blink
LED Continuous Blink : 0.1sec ON / 0.1sec OFF blinking
LED Blink (2 to 14 times) : 0.5sec ON / 0.5sec OFF blinking
(RED)
(GREEN)
(ORANGE)
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...