Trouble shooting 12
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Outdoor Unit : LED 9 times blink
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 :
Check Point 2 : Check voltage of Main PCB (DC5.0V)
HIGH PRESSURE SW
BLACK
BLACK
RED
RED
CN37
1
2
1
2
3
4WV
OK
Check Point 1 :
Reset Power Supply and operate
Check Point 3 : Check Pressure Switch
YES
YES
NO
NO
Pressure Switch Error
Outdoor Unit Main PCB Circuit
Pressure Switch
1. Connector connection failure 2. Pressure Switch failure 3. Main PCB failure
When pressure switch open is detected in 10 seconds
after the power is turned on.
Does abnormal LED indication show again?
Make sure circuit diagram of outdoor unit and check terminal voltage
at Pressure Switch. (DC5.0V)
If the voltage does not appear, replace Main PCB.
Check if connector is loose or cable is open.
>> If no abnormal connection is found,
replace Pressure Switch.
After replacing Pressure Switch, check operating
condition and pressure in operation.
07-13
Indoor Unit : Operation LED: Blink, Timer LED: 9 times blink,
Vertical swing LED: OFF
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...