08-04
OUTDOOR UNIT
PROTECTION FORM
AO*30LMBWL
AO*36LMBWL
FUSE (SIDE OF POWER SUPPLY TERMINAL)
-
25A 250V
25A 250V
FUSE (SIDE OF INDOOR UNIT)
-
10A 250V
10A 250V
-
3.15A 250V
3.15A 250V
-
5A 250V
5A 250V
FAN MOTOR PROTECTOR
THERMAL PROTECTOR
150±5°C OFF
150±5°C OFF
HIGH PRESSURE PROTECTION
PRESSURE SWITCH
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
DISCHARGE THERMISTOR
THERMAL PROTECTOR
OFF:120±5°C
ON:80±5°C
OFF:120±5°C
ON:80±5°C
COMPRESSOR THERMISTOR
THERMAL PROTECTOR
OFF:130±5°C
ON:80±5°C
OFF:130±5°C
ON:80±5°C
FUSE ON MAIN PCB
INDOOR UNIT
PROTECTION FORM
AB*30LBAG
AB*36LBAG
PCB FUSE
-
FAN MOTOR PROTECTION
PROTECTION FORM
AO*45LJBYL
FUSE
(SIDE OF INDOOR UNIT TERMINAL)
-
10A 250V
-
3.15A 250V
3.15A 250V
-
5A 250V
FAN MOTOR PROTECTOR
THERMAL PROTECTOR
150±5°C OFF
120±5°C OFF
HIGH PRESSURE PROTECTION
PRESSURE SWITCH
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
DISCHARGE THERMISTOR
THERMAL PROTECTOR
OFF:120±5°C
ON:80±5°C
COMPRESSOR THERMISTOR
THERMAL PROTECTOR
THERMAL PROTECTOR
PROTECTION FORM
AB*45LBAG
PCB FUSE
-
FAN MOTOR PROTECTION
3.15A 250V
120±5°C OFF
THERMAL PROTECTOR
OFF:130±5°C
ON:80±5°C
FUSE ON MAIN PCB
8-4. SAFETY DEVICE
Summary of Contents for AB*30LBAG series
Page 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Page 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Page 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Page 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...