5-3. DRY OPERATION
5-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
Room
temperature
Room
temperature
Compressor ON
Ts+1.5 degC
Ts+1 degC
Compressor OFF
Compressor
ON
ON
OFF
Indoor fan
air flow mode
Air flow mode : Lo
OFF
30 5 30 120 5 (sec)
180 180
( Table 3 : Compressor frequency )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
05-03
Operating frequency
45Hz
45Hz
30Hz
AB*30LBAG
AB*36LBAG
AB*45LBAG
Ts : Setting temperature