27
Chapter6
Setting
The following setting can be changed in any mode with an operation
panel of UPS.
No
Item
Default
①
External Battery module(EBM) set
0set
②
REPO / REMOTE
Invalidity
③
UTL failure signal delay
0 second
④
Output delay
0 second
⑤
Rated Voltage
100V
⑥
Mode select
Normal
⑦
Synchronized range
±3Hz
⑧
AUTOSTART after shutdown with alarm
Effective
⑨
Polarity
Active close
⑩
Buzzer stop
No active
⑪
AUTOSTART
Effective
⑫
Auto battery test
Effective
⑬
Remote shut down signal term
4.5seconds
⑭
Manual Bypass
Invalidity
⑮
Voltage range of HE mode
±5%
⑯
Frequency range of HE mode
±1Hz
⑰
Language
Japanese
⑱
DC start
Invalidity
・When the power cable is pulled out no battery, content of setting change is not
preserved.
・Only ⑥ can be changed from the network agent card by the communication.
This change becomes a compulsion change.