51
The UPS offers four relay (Input abnormal, Low battery, UPS alarm, On-Bypass).
The signal can output the open or the close. Moreover, it provides with the
terminal of REPO (REMOTE ON/OFF) and a Remote Shutdown.
Table 9-2 Terminal on PCB(M4)
No
Terminal
Signal
I/O
Jumper
Relay
Note
1-2
OPEN
1
P1-P2
Input
abnormal
Out
JP1
3-2
CLOSE
1-2
OPEN
2
P3-P4
Low
battery
Out
JP2
3-2
CLOSE
1-2
OPEN
3
P5-P6
UPS alarm
Out
JP3
3-2
CLOSE
1-2
OPEN
JP4
3-2
CLOSE
DC30V MAX 2A MAX
AC125V MAX 0.5A MAX
1-2
-
On-Bypass output possible
4
P7-P8
On-Bypass
Out
JP5
3-2
-
On-Bypass output impossible
・Choose the ring tongue terminal of the size that suits M4
・Cover and mount the sleeve on the ring tongue terminal.
Table 9-3 Terminal
No
Terminal
Signal
I/O
Spec
Note
5
REPO
REPO
REMOTE ON/OFF
In
10mA MAX
This is used for an urgent stop or
remote ON/OFF.
6
RSD
Remote shut
down
In
5V~30V
When remotely shutting down, This is
used.
Prepare the line kind of the following condition in the connection to this terminal.
Table 9-4 Condition
Item
Content
Kind
Twist or Shield
DIA
AWG22~16
Torque
5 lbf・in
Screw
M3
Stripping Length
6~7mm
・Defend and use the connection condition and the signal specification. There is a
possibility of damaging it besides.
・Do the static electricity measures when you connect it.