54
9-2-4 Low battery
When Low-Battery is detected, the UPS turns on relay contact of
Low-Battery. Open/Close output is possible according to Jumper 2.
The contact spec is (30VDC MAX-2AMAX, 125VACMAX-0.5AMAX).
・Do not deviate from the contact specification. The card is damaged.
・ The connecting cable must use the twist or shield for the malfunction
prevention.
9-2-5 On-Bypass
When On-Bypass is detected, the UPS turns on relay contact of
On-Bypass. Open/Close output is possible according to Jumper 4,5.
The contact spec is (30VDC MAX-2AMAX, 125VACMAX-0.5AMAX).
・Do not deviate from the contact specification. The card is damaged.
・ The connecting cable must use the twist or shield for the malfunction
prevention.
・This relay is turned on to the output status by the manual bypass.
9-2-6 Input abnormal
When input abnormal is detected, the UPS turns on relay contact of input
abnormal. Open/Close output is possible according to Jumper 1.
The contact spec is (30VDC MAX-2AMAX, 125VACMAX-0.5AMAX).
・Do not deviate from the contact specification. The card is damaged.
・ The connecting cable must use the twist or shield for the malfunction
prevention.
9-2-7 UPS alarm
When Alarm is detected, the UPS turns on relay contact of input abnormal.
Open/Close output is possible according to Jumper 3.
The contact spec is (30VDC MAX-2AMAX, 125VACMAX-0.5AMAX).
・Do not deviate from the contact specification. The card is damaged.
・ The connecting cable must use the twist or shield for the malfunction
prevention.
・ On-Line impossible continuance by the overload and the manual bypass is
excluded.