CLOCK= / CLOCK? (Not Yet Implemented) {F008}
Define or query the existence of Real Time Clock hardware.
CLRALARM
Clear alarm conditions from the system, if any exist. Restore ALMCODE? to 0. If the condition creating
the alarm state persists, however, the system will restore the alarm until that condition is corrected.
CPB= / CPB? {F010}
Set or query the width, in degrees, of the band about setpoint (SP) over which the control system will
proportion the cooling valves (Cool Proportioning Band).
CTLREM= / CTLREM? {F011}
Set or query the use of the remote sensor for temperature control of the system. Value 0 (off) means
"control from the internal sensor"; 1 (on) means "control from the remote sensor". If the remote sensor is
not connected (open circuit), the system will automatically revert to internal-sensor control and an alarm
will result.
CURRSNS? (Service Use) {F012}
Query the existence of pump/compressor current sensors as defined by the system hardware complement
(factory set). 0 = off/don't exist; 1 = on.
DATE= / DATE? (Not Yet Implemented) {F013}
Set or query date in Real Time Clock option.
DB= / DB? {F014}
Set or query the deadband, in degrees, between the heat and cool proportioning bands (HPB/CPB). This
value is usually negative, implying overlap.
DEFAULT (Not Yet Implemented)
Restore factory default values to the programmable parameter table.
DEGREES= / DEGREES? {F016}
Set or query the temperature scale used on the display and in further RS-232 communications. 0 = Celsius,
1 = Fahrenheit, 2 = Kelvin.
DP= / DP? {F017}
Set or query the use of integer/decimal format on the control panel display. 0 (decimal point off) displays
temperature rounded to the nearest integer; 1 (decimal point on) displays temperature with 0.1 resolution.
DT= / DT? {F018}
Set or query, in seconds, the [derivative] time constant applied to the proportioning band adjustment, as a
function of rate of change in the process temperature.
FLUID= / FLUID? {F019}
Set or query the number defining the fluid type in use in the system (see system programming
documentation for a listing). Fluid definition automatically sets FSPANH and FSPANL, subject to
SSPANH and SSPANL, to limit the permissible bounds of the setpoint SP and the alarm temperatures
ALARMH and ALARML.
FORMAT= / FORMAT? (Not implemented / obsolete) {F020}
Describes the format of transmitted data. Task offloaded to the host processor.
FSPANH? {F021}
Query the high temperature limit (degrees) established by the FLUID definition.